EMT conduit fill
EMT Copper THHN NEC 2023
Fill chart
Select a count to calculate.
Conduit trade size
| Wire gauge | ½″ | ¾″ | 1″ | 1¼″ | 1½″ | 2″ |
|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 26 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 |
| 1/0 AWG | 1 | 1 | 1 | 3 | 4 | 7 |
Maximum counts for same-gauge copper THHN.
Fill calculator
EMT trade size
Reference preview for ordinary EMT runs with copper THHN. Account for all conductors before using a result.
Calculation details
How to use the EMT fill chart
Choose the EMT trade size and find the row for your copper THHN wire gauge. Each count assumes all conductors have the same insulated cross-sectional area. Tap a count to check that combination in the calculator.
Checking a mix of wire sizes
Add a group for each supported wire gauge. The calculator adds their insulated areas and compares the total with the fill limit for the number of conductors. Changing the EMT size keeps the same wire groups. Near-limit mixed results prompt a Table 4 check.
Example
Eight 12 AWG and three 10 AWG copper THHN conductors occupy 0.1697 in². In ¾″ EMT the reference fill is about 31.8%. The calculation details show each group and the EMT area used.