EMT conduit fill

EMT Copper THHN NEC 2023

Fill chart

Select a count to calculate.

Conduit trade size

Maximum matching copper THHN conductors by wire gauge and EMT trade size
Wire gauge½″¾″1″1¼″1½″2″2½″3″3½″4″
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG247121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532

Maximum counts for same-gauge copper THHN.

Fill calculator

EMT trade size

Conduit fill
—
Base limit—
Smallest listed EMT—

Reference preview for ordinary EMT runs with copper THHN. Account for all conductors before using a result.

Calculation details

How to use the EMT fill chart

Choose the EMT trade size and find the row for your copper THHN wire gauge. Each count assumes all conductors have the same insulated cross-sectional area. Tap a count to check that combination in the calculator.

Checking a mix of wire sizes

Add a group for each supported wire gauge. The calculator adds their insulated areas and compares the total with the fill limit for the number of conductors. Changing the EMT size keeps the same wire groups. Near-limit mixed results prompt a Table 4 check.

Example

Eight 12 AWG and three 10 AWG copper THHN conductors occupy 0.1697 in². In ¾″ EMT the reference fill is about 31.8%. The calculation details show each group and the EMT area used.