¾-Inch EMT Conduit Fill Chart
EMT Copper THHN NEC 2023
For ordinary ¾-inch EMT, the reference maximum is 16 matching 12 AWG copper THHN conductors. For 10 AWG copper THHN, the maximum is 10.
Maximum copper THHN counts
| Wire gauge | Maximum count |
|---|---|
| 14 AWG | 22 |
| 12 AWG | 16 |
| 10 AWG | 10 |
| 8 AWG | 6 |
| 6 AWG | 4 |
| 4 AWG | 2 |
| 3 AWG | 1 |
| 2 AWG | 1 |
| 1 AWG | 1 |
| 1/0 AWG | 1 |
Which count applies?
Use one row when all wires have the same insulated dimensions. For ordinary EMT, the fill limit is 53% for one conductor, 31% for two and 40% for three or more. The counts apply the same-size rounding provision in NEC Chapter 9, Note 7 where applicable.
When your run includes different wire sizes or insulation types, add the occupied areas. Include grounding conductors and any other conductors that occupy the raceway. This reference covers copper THHN in ordinary EMT runs. Verify the rules adopted for your job. See a mixed-wire example.