Conduit Fill for Mixed Wire Sizes

EMT Copper THHN NEC 2023

Eight 12 AWG and three 10 AWG copper THHN conductors use 31.8% of ¾-inch EMT. The same wires use 55.8% of ½-inch EMT and exceed its fill limit.

Add the conductor areas

The two groups occupy 0.1697 in² in total. They contain 11 conductors, so the ordinary-run fill limit is 40% under the 2023 NEC reference.

Compare ½-inch and ¾-inch EMT

Divide the occupied area by 0.304 in² for ½-inch EMT or 0.533 in² for ¾-inch EMT. Multiply by 100 and compare the result with the 40% limit for this run.

Fill comparison for the same 11 conductors in two EMT trade sizes
EMTFillFill check
½″55.8%Over limit
¾″31.8%Within limit

Open this example in the calculator

Check what else occupies the raceway

The two groups shown are all the conductors in this example. Include an equipment grounding conductor and any other wires or cables when present. Verify the published allowable area in Chapter 9, Table 4 for a result near the limit. Special cases such as short nipples have different rules. Verify the adopted code before using the result for a job.

For a run of matching copper THHN conductors, look up the count in the ¾-inch EMT fill chart.