Conduit Fill for Mixed Wire Sizes
EMT Copper THHN NEC 2023
Eight 12 AWG and three 10 AWG copper THHN conductors use 31.8% of ¾-inch EMT. The same wires use 55.8% of ½-inch EMT and exceed its fill limit.
Add the conductor areas
- 8 × 12 AWG at 0.0133 in² each = 0.1064 in²
- 3 × 10 AWG at 0.0211 in² each = 0.0633 in²
The two groups occupy 0.1697 in² in total. They contain 11 conductors, so the ordinary-run fill limit is 40% under the 2023 NEC reference.
Compare ½-inch and ¾-inch EMT
Divide the occupied area by 0.304 in² for ½-inch EMT or 0.533 in² for ¾-inch EMT. Multiply by 100 and compare the result with the 40% limit for this run.
| EMT | Fill | Fill check |
|---|---|---|
| ½″ | 55.8% | Over limit |
| ¾″ | 31.8% | Within limit |
Check what else occupies the raceway
The two groups shown are all the conductors in this example. Include an equipment grounding conductor and any other wires or cables when present. Verify the published allowable area in Chapter 9, Table 4 for a result near the limit. Special cases such as short nipples have different rules. Verify the adopted code before using the result for a job.
For a run of matching copper THHN conductors, look up the count in the ¾-inch EMT fill chart.