EMT Conduit Fill Chart

EMT Copper THHN NEC 2023

Look up the maximum number of same-size copper THHN conductors in ordinary EMT from ½″ to 4″. Compare sizes in the table, or select a trade size to open the interactive chart for that column.

Maximum copper THHN counts

Scroll the chart horizontally to see more sizes.

Maximum counts for same-size copper THHN by EMT trade size
Wire gauge½″¾″1″1¼″1½″2″2½″3″3½″4″
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG247121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532

Use the chart for matching conductors

Choose the wire gauge and the EMT trade size. The number at the intersection is the maximum for that combination when all conductors have the same insulated dimensions. A zero means even one conductor exceeds the fill allowance. Count grounding conductors and everything else occupying the raceway.

For a mix of wire sizes or insulation types, add the occupied areas and compare the result with the applicable fill limit. Check the code edition and local amendments adopted for the job.