EMT Conduit Fill Chart
EMT Copper THHN NEC 2023
Look up the maximum number of same-size copper THHN conductors in ordinary EMT from ½″ to 4″. Compare sizes in the table, or select a trade size to open the interactive chart for that column.
Maximum copper THHN counts
Scroll the chart horizontally to see more sizes.
| Wire gauge | ½″ | ¾″ | 1″ | 1¼″ | 1½″ | 2″ | 2½″ | 3″ | 3½″ | 4″ |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
| 1/0 AWG | 1 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 32 |
Use the chart for matching conductors
Choose the wire gauge and the EMT trade size. The number at the intersection is the maximum for that combination when all conductors have the same insulated dimensions. A zero means even one conductor exceeds the fill allowance. Count grounding conductors and everything else occupying the raceway.
For a mix of wire sizes or insulation types, add the occupied areas and compare the result with the applicable fill limit. Check the code edition and local amendments adopted for the job.